Parameter |
Values (Range) |
Unit |
Step |
Default |
Description |
---|---|---|---|---|---|
Current value |
0.05...2.00 |
xIn |
0.01 |
0.30 |
Operating phase current |
Current value Res |
0.05...2.00 |
xIn |
0.01 |
0.30 |
Operating residual current |
CB failure trip mode |
1=2 out of 4 2=1 out of 3 3=1 out of 4 |
2=1 out of 3 |
Backup trip current check mode |
||
CB failure mode |
1=Current 2=Breaker status 3=Both (AND) -1=Both (OR) |
1=Current |
Operating mode of function |
||
CB fail retrip mode |
1=Off 2=Without Check 3=Current check |
1=Off |
Operating mode of retrip logic |
||
Retrip time |
0...60000 |
ms |
10 |
120 |
Delay timer for retrip |
CB failure delay |
0...60000 |
ms |
10 |
240 |
Delay timer for backup trip |
Operation |
1=on 5=off |
1=on |
Operation Off / On |
Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
CB fault delay | 0...60000 | ms | 10 | 5000 | Circuit breaker faulty delay |
Measurement mode |
2=DFT 3=Peak-to-Peak |
3=Peak-to-Peak | Phase current measurement mode of function | ||
Trip pulse time | 0...60000 | ms | 10 | 200 | Pulse length of retrip and backup trip outputs |
Start latching mode |
1=Rising edge 2=Level sensitive |
1=Rising edge | Start reset delayed or immediately |