Settings - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - IEC - ANSI - 12.12.2023

REX610 Technical Manual

Table 1. EFLPTOC Group settings (Basic)

Parameter

Values (Range)

Unit

Step

Default

Description

Start value

0.010...5.000

xIn

0.005

0.010

Start value

Start value Mult

0.8...10.0

0.1

1.0

Multiplier for scaling the start value

Operating curve type

1=ANSI Ext. inv.

2=ANSI Very inv.

3=ANSI Norm. inv. .

4=ANSI Mod. inv.

5=ANSI Def. Time

6=L.T.E. inv.

7=L.T.V. inv.

8=L.T. inv.

9=IEC Norm. inv.

10=IEC Very inv.

11=IEC inv.

12=IEC Ext. inv.

13=IEC S.T. inv.

14=IEC L.T. inv.

15=IEC Def. Time

17=Programmable

18=RI type

19=RD type

15=IEC Def. Time

Selection of time delay curve type

Time multiplier

0.05...15.00

0.01

1.00

Time multiplier in IEC/ANSI IDMT curves

Operate delay time

40...300000

ms

10

40

Operate delay time

Table 2. EFLPTOC Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Type of reset curve

1=Immediate

2=Def time reset

3=Inverse reset

1=Immediate Selection of reset curve type

Table 3. EFLPTOC Non group settings (Basic)

Parameter

Values (Range)

Unit

Step

Default

Description

Operation

1=on

5=off

1=on

Operation Off / On

Curve parameter A

0.0086...120.0000

0.0001

28.2000

Parameter A for customer programmable curve

Curve parameter B

0.0000...0.7120

0.0001

0.1217

Parameter B for customer programmable curve

Curve parameter C

0.02...2.00

0.01

2.00

Parameter C for customer programmable curve

Curve parameter D

0.46...30.00

0.01

29.10

Parameter D for customer programmable curve

Curve parameter E

0.0...1.0

0.1

1.0

Parameter E for customer programmable curve

Table 4. EFLPTOC Non group settings (Advanced)

Parameter

Values (Range)

Unit

Step

Default

Description

Measurement mode

1=RMS

2=DFT

3=Peak-to-Peak

2=DFT

Selects used measurement mode

Minimum operate time

20...60000

ms

1

20

Minimum operate time for IDMT curves

Reset delay time

0...60000

ms

1

20

Reset delay time

Table 5. EFHPTOC Group settings (Basic)

Parameter

Values (Range)

Unit

Step

Default

Description

Start value

0.10...40.00

xIn

0.01

0.10

Start value

Start value Mult

0.8...10.0

0.1

1.0

Multiplier for scaling the start value

Operating curve type

1=ANSI Ext. inv.

3=ANSI Norm. inv.

5=ANSI Def. Time

9=IEC Norm. inv.

10=IEC Very inv.

12=IEC Ext. inv.

15=IEC Def. Time

17=Programmable

15=IEC Def. Time

Selection of time delay curve type

Time multiplier

0.05...15.00

0.01

1.00

Time multiplier in IEC/ANSI IDMT curves

Operate delay time

40...300000

ms

10

40

Operate delay time

Table 6. EFHPTOC Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Type of reset curve

1=Immediate

2=Def time reset

3=Inverse reset

1=Immediate Selection of reset curve type

Table 7. EFHPTOC Non group settings (Basic)

Parameter

Values (Range)

Unit

Step

Default

Description

Operation

1=on

5=off

1=on

Operation Off / On

Curve parameter A

0.0086...120.0000

0.0001

28.2000

Parameter A for customer programmable curve

Curve parameter B

0.0000...0.7120

0.0001

0.1217

Parameter B for customer programmable curve

Curve parameter C

0.02...2.00

0.01

2.00

Parameter C for customer programmable curve

Curve parameter D

0.46...30.00

0.01

29.10

Parameter D for customer programmable curve

Curve parameter E

0.0...1.0

0.1

1.0

Parameter E for customer programmable curve

Table 8. EFHPTOC Non group settings (Advanced)

Parameter

Values (Range)

Unit

Step

Default

Description

Measurement mode

1=RMS

2=DFT

3=Peak-to-Peak

2=DFT

Selects used measurement mode

Minimum operate time

20...60000

ms

1

20

Minimum operate time for IDMT curves

Reset delay time

0...60000

ms

1

20

Reset delay time

Table 9. EFIPTOC Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Start value 1.00...40.00 xIn 0.01 1.00 Start value
Start value Mult 0.8...10.0 0.1 1.0 Multiplier for scaling the start value
Operate delay time 20...300000 ms 10 20 Operate delay time

Table 10. EFIPTOC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation

1=on

5=off

1=on Operation Off / On

Table 11. EFIPTOC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time