Settings - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - 1.2 - IEC - ANSI - 12.12.2023

REX610 Technical Manual

Table 1. PHPTOV Group settings (Basic)

Parameter

Values (Range)

Unit

Step

Default

Description

Operating curve type

5=ANSI Def. Time

15=IEC Def. Time

17=Inv. Curve A

18=Inv. Curve B

19=Inv. Curve C

20=Programmable

15=IEC Def. Time

Selection of time delay curve type

Time multiplier

0.05...15.00

0.01

1.00

Time multiplier in IEC/ANSI IDMT curves

Start value

0.05...1.60

xUn

0.01

1.10

Start value

Operate delay time

40...300000

ms

10

40

Operate delay time

Table 2. PHPTOV Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Type of reset curve

1=Immediate

2=Def time reset

1=Immediate Selection of reset curve type
Type of time reset

1=Freeze Op timer

2=Decrease Op timer

1=Freeze Op timer Selection of time reset

Table 3. PHPTOV Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation

1=on

5=off

1=on Operation Off / On
Num of start phases

1=1 out of 3

2=2 out of 3

3=3 out of 3

1=1 out of 3 Number of phases required for operate activation
Curve parameter A 0.005...200.000 0.001 1.000 Parameter A for customer programmable curve
Curve parameter B 0.50...100.00 0.01 1.00 Parameter B for customer programmable curve
Curve parameter C 0.0...1.0 0.1 0.0 Parameter C for customer programmable curve
Curve parameter D 0.000...60.000 0.001 0.000 Parameter D for customer programmable curve
Curve parameter E 0.000...3.000 0.001 1.000 Parameter E for customer programmable curve
Voltage selection

1=phase-to-earth

2=phase-to-phase

2=phase-to-phase Parameter to select phase or phase-to-phase voltages

Table 4. PHPTOV Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Minimum operate time 40...60000 ms 1 40 Minimum operate time for IDMT curves
Reset delay time 0...60000 ms 1 20 Reset delay time
Curve Sat Relative 0.0...10.0 0.1 0.0 Tuning parameter to avoid curve discontinuities
Relative hysteresis 1.0...5.0 % 0.1 4.0 Relative hysteresis for operation