Table 1. RESVMMXU Non group settings (Basic)

Parameter

Values (Range)

Unit

Step

Default

Description

V Hi high limit res

0.00...4.00

xUn

0.01

0.20

High alarm voltage limit

V high limit res

0.00...4.00

xUn

0.01

0.05

High warning voltage limit

V deadband res

100...100000

1

10000

Deadband configuration value for integral calculation. (percentage of difference between min and max as 0,001 % s)

Operation

1=on

5=off

1=on

Operation Off / On

Table 2. RESVMMXU Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Measurement mode

1=RMS

2=DFT

2=DFT Selects used measurement mode
On delay time 0...1800000 ms 100 0 Delay the activation of the alarm and warning outputs
Off delay time 0...1800000 ms 100 0 Delay the deactivation of the alarm and warning outputs