Table 1. INRPHAR Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Start value 5...100 % 1 20 Ratio of the 2. to the 1. harmonic leading to restraint
Operate delay time 20...60000 ms 1 20 Operate delay time

Table 2. INRPHAR Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation

1=on

5=off

1=on Operation Off / On

Table 3. INRPHAR Non group settings (Advanced)

Parameter

Values (Range)

Unit

Step

Default

Description

Reset delay time

0...60000

ms

1

20

Reset delay time