Parameter |
Values (Range) |
Unit |
Step |
Default |
Description |
---|---|---|---|---|---|
Time constant |
60...60000 |
s |
1 |
2700 |
Time constant of the line in seconds. |
Current reference |
0.05...4.00 |
xIn |
0.01 |
1.00 |
The load current leading to Temperature raise temperature |
Temperature rise |
0.0...200.0 |
°C |
0.1 |
75.0 |
End temperature rise above ambient |
Env temperature Set |
-50...100 |
°C |
1 |
40 |
Ambient temperature used when no external temperature measurement available |
Alarm value |
20.0...150.0 |
°C |
0.1 |
80.0 |
Temperature level for start (alarm) |
Maximum temperature |
20.0...200.0 |
°C |
0.1 |
90.0 |
Temperature level for operate |
Reclose temperature |
20.0...150.0 |
°C |
0.1 |
70.0 |
Temperature for reset of block reclose after operate |
Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Current multiplier | 1...5 | 1 | 1 | Current multiplier when function is used for parallel lines |
Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Operation |
1=on 5=off |
1=on | Operation Off / On |
Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Initial temperature | -50.0...100.0 | °C | 0.1 | 0.0 | Temperature raise above ambient temperature at startup |