The protection relay supports four setting groups. Each setting group contains parameters categorized as group settings inside application functions. The customer can change the active setting group at run time.
The active setting group can be changed by a parameter or via binary inputs depending on the mode selected with the
setting.The default value of all inputs is FALSE, which makes it possible to use only the required number of inputs and leave the rest disconnected. The setting group selection is not dependent on the SG_x_ACT outputs.
SG operation mode |
Description |
---|---|
Operator (Default) |
Setting group can be changed with the setting Settings/Setting group/Active group. Value of the SG_LOGIC_SEL output is FALSE. |
Logic mode 1 |
Setting group can be changed with binary inputs (BI_SG_2...BI_SG_4). The highest TRUE binary input defines the active setting group. Value of the SG_LOGIC_SEL output is TRUE. |
Input |
|||
---|---|---|---|
BI_SG_2 |
BI_SG_3 |
BI_SG_4 |
Active group |
FALSE |
FALSE |
FALSE |
1 |
TRUE |
FALSE |
FALSE |
2 |
any |
TRUE |
FALSE |
3 |
any |
any |
TRUE |
4 |
Setting group 1 can be copied to any other or all groups from HMI (Copy group 1).