Sampling frequencies - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - IEC - ANSI - 03.05.2023

REX610 Technical Manual

The sampling frequency of the disturbance recorder analog channels depends on the set rated frequency. One fundamental cycle always contains the number of samples set with the Storage rate parameter. Since the states of the binary channels are sampled once per task execution of the disturbance recorder, the sampling frequency of binary channels is 200 Hz at the rated frequency of 50 Hz and 240 Hz at the rated frequency of 60 Hz.

Table 1. Sampling frequencies of the disturbance recorder analog and binary channels

Storage rate (samples per fundamental cycle)

Recording length

Rated frequency = 50 Hz

Rated frequency = 60 Hz

Sampling frequency of analog channels

Sampling frequency of binary channels

Sampling frequency of analog channels

Sampling frequency of binary channels

32

1 · Record length

1600 Hz

200 Hz

1920 Hz

240 Hz

16

2 · Record length

800 Hz

200 Hz

960 Hz

240 Hz

8

4 · Record length

400 Hz

200 Hz

480 Hz

240 Hz