Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Motor start-up A | 1.0...10.0 | xIn | 0.1 | 2.0 | Motor starting current |
Motor start-up time | 1...80 | s | 1 | 5 | Motor starting time |
Lock rotor time | 2...120 | s | 1 | 10 | Permitted stalling time |
Str over delay time | 0...60000 | ms | 1 | 100 | Time delay to check for completion of motor startup period |
Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Start detection A | 0.1...10.0 | xIn | 0.1 | 1.5 | Current value for detecting starting of motor. |
Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Operation |
1=on 5=off |
1=on | Operation Off / On | ||
Operation mode |
1=IIt 2=IIt, CB 3=IIt + stall 4=IIt + stall, CB |
1=IIt | Motor start-up operation mode | ||
Counter Red rate | 2.0...250.0 | s/h | 0.1 | 60.0 | Start time counter reduction rate |
Cumulative time Lim | 1...500 | s | 1 | 10 | Cumulative time based restart inhibit limit |
Emg start Red rate | 0.00...100.00 | % | 0.01 | 20.00 | Start time reduction factor when emergency start is On |
Restart inhibit time | 0...250 | min | 1 | 30 | Time delay between consecutive startups |
Ini start up counter | 0...999999 | 1 | 0 | Initial value for the START_CNT |
Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Motor standstill A | 0.05...0.20 | xIn | 0.01 | 0.12 | Current limit to check for motor standstill condition |