STTPMSU Monitored data - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - IEC - ANSI - 03.05.2023

REX610 Technical Manual

Table 1. STTPMSU Monitored data
Name Type Values (Range) Unit Description
START_CNT INT32 0...999999 Number of motor start-ups occurred
START_TIME FLOAT32 0.0...999.9 s Measured motor latest startup time in sec
T_ST_CNT FLOAT32 0.0...99999.9 s Cumulated start-up time in sec
T_RST_ENA INT32 0...999 min Time left for restart when lockstart is enabled in minutes
IIT_RL FLOAT32 0.00...100.00 % Thermal stress relative to set maximum thermal stress
STALL_RL FLOAT32 0.00...100.00 % Start time relative to the operate time for stall condition
STTPMSU1 Enum

1=on

2=blocked

3=test

4=test/blocked

5=off

Status