The user can select the reset characteristics by using the Type of reset curve setting.
Setting name | Possible values |
---|---|
Type of reset curve |
1=Immediate 2=Def time reset 3=Inverse reset |
Immediate reset
If the Type of reset curve setting in a drop-off case is selected as "Immediate", the inverse timer resets immediately.
Definite time reset
The definite type of reset in the inverse-time mode can be achieved by setting the Type of reset curve parameter to “Def time reset”. As a result, the operate inverse-time counter is frozen for the time determined with the Reset delay time setting after the current drops below the set Start value, including hysteresis. The integral sum of the inverse-time counter is reset, if another start does not occur during the reset delay.
Inverse reset
Standard delayed inverse reset
The reset characteristic required in ANSI (IEEE) inverse-time modes is provided by setting the Type of reset curve parameter to “Inverse reset”. In this mode, the time delay for reset is given with the following formula using the coefficient D, which has its values defined in the table below.
t[s] | Reset time (in seconds) |
k | Set Time multiplier |
I | Measured current |
I> | Set Start value |
Curve name | D |
---|---|
(1) ANSI Extremely Inverse | 29.1 |
(2) ANSI Very Inverse | 21.6 |
(3) ANSI Normal Inverse | 0.46 |
(4) ANSI Moderately Inverse | 4.85 |
(6) Long Time Extremely Inverse | 30 |
(7) Long Time Very Inverse | 13.46 |
(8) Long Time Inverse | 4.6 |
The delayed inverse reset time depends also on the protection function's start duration value START_DUR. The reset time on the drop-off moment can be calculated by multiplying t[s] with START_DUR.
User-programmable delayed inverse reset
The user can define the delayed inverse reset time characteristics with the following formula using the set Curve parameter D.
The delayed inverse reset time depends also on the protection function's start duration value START_DUR. The reset time on the drop-off moment can be calculated by multiplying t[s] with START_DUR.
t[s] | Reset time (in seconds) |
k | Set Time multiplier |
D | Set Curve parameter D |
I | Measured current |
I> | Set Start value |