The relay has mandatory and optional slots. A mandatory slot always contains a module but an optional slot may be empty, depending on the composition variant ordered.
Module |
Slot A1 |
Slot A2 |
Slot B |
Slot C1 |
Slot C2 |
Slot D1 |
Slot D2 |
---|---|---|---|---|---|---|---|
AIC2001 |
o |
||||||
AIC2002 |
o |
||||||
AIU2001 |
o |
||||||
ARC2001 |
o |
||||||
COM2001 |
● |
||||||
DIO2001 |
● |
||||||
PSU2001 |
● |
● = Mandatory to have the modules in the slot
o = Optional to have one of the allocated modules in the slot
Module | Description |
---|---|
AIU2001 | Analog input 4 × VT compression |
AIC2001 | Analog input 4 × CT compression |
AIC2002 | Analog input 4 × CT ring lug |
PSU2001 | 24...250 VDC / 48...240 VAC + 2 × PO |
DIO2001 | Digital I/O 6 × BI + 4 × SO |
COM2001 | 1 × RJ-45 + 1 × RS-485 |
ARC2001 | 3 arc sensor inputs |
PO = Power Output SO = Signal Output |
The relay has a nonvolatile memory which does not need any periodical maintenance. The nonvolatile memory stores all events, recordings and logs to a memory which retains data if the relay loses its auxiliary supply.