RESTCTR Settings - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - IEC - ANSI - 03.05.2023

REX610 Technical Manual

Table 1. RESTCTR Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Primary current 1.0...6000.0 A 0.1 100.0 Primary current
Secondary current 0.10...10.00 A 0.01 1.00 Secondary current
Amplitude Corr 0.9000...1.1000 0.0001 1.0000 Amplitude correction
Angle correction -8.0000...8.0000 deg 0.0001 0.0000 Angle correction factor
Table 2. RESTCTR Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reverse polarity

0=False

1=True

0=False Reverse the polarity of the residual CT