Description |
Type test value |
Reference |
---|---|---|
1 MHz/100 kHz burst disturbance test Common mode |
2.5 kV |
IEC 61000-4-18 IEC 60255-26, class III IEEE C37.90.1-2012 |
1 MHz/100 kHz burst disturbance test Differential mode |
2.5 kV |
|
3 MHz, 10 MHz and 30 MHz burst disturbance test Common mode |
2.5 kV |
IEC 61000-4-18 |
Electrostatic discharge test Contact discharge |
8 kV |
IEC 61000-4-2 IEC 60255-26 IEEE C37.90.3-2001 |
Electrostatic discharge test Air discharge |
15 kV |
|
Radio frequency interference test Conducted RF |
10 V (rms) f = 150 kHz...80 MHz |
IEC 61000-4-6 IEC 60255-26, class III |
Radio frequency interference test Radiated RF |
10 V/m (rms) f = 80...2700 MHz |
IEC 61000-4-3 IEC 60255-26, class III |
20 V/m f = 900 MHz |
ENV 50204 |
|
20 V/m (rms) f = 80...1000 MHz |
IEEE C37.90.2-2004 |
|
Fast transient disturbance test Communication |
2 kV |
IEC 61000-4-4 IEC 60255-26 IEEE C37.90.1-2002 |
Fast transient disturbance test Other ports |
4 kV |
|
Surge immunity test Communication |
4 kV, line-to-earth |
IEC 61000-4-5 IEC 60255-26 |
Surge immunity test Other ports |
4 kV, line-to-earth |
|
2 kV, line-to-line |
||
Power frequency (50 Hz) magnetic field immunity test Continuous |
300 A/m |
IEC 61000-4-8 |
Power frequency (50 Hz) magnetic field immunity test 1...3 s |
1000 A/m |
|
Pulse magnetic field immunity test |
1000 A/m 6.4/16 µs |
IEC 61000-4-9 |
Damped oscillatory magnetic field immunity test Continuous and 2 s |
Current oscillation frequency: 100 kHz and 1 MHz Current rise time: 75 ns Repetition frequency: 40 Hz (100 Hz) and 400 Hz (1 MHz) Polarity of first half period: Positive and Negative |
IEC 61000-4-10 |
Voltage dips and short interruptions |
30%/10 ms 60%/100 ms 60%/1000 ms >95%/5000 ms |
IEC 61000-4-11 |
Power frequency immunity test Common mode |
Binary inputs only 300 V rms |
IEC 61000-4-16 IEC 60255-26, class A |
Power frequency immunity test Differential mode |
Binary inputs only 150 V rms |
|
Emission tests Conducted 0.15...0.50 MHz |
<79 dB (µV) quasi peak <66 dB (µV) average |
EN 55011, class A IEC 60255-26 CISPR 11 CISPR 22 |
Emission tests Conducted 0.5...30 MHz |
<73 dB (µV) quasi peak <60 dB (µV) average |
|
Emission tests Radiated 30...230 MHz |
<40 dB (µV/m) quasi peak, measured at 10 m distance |
|
Emission tests Radiated 230...1000 MHz |
<47 dB (µV/m) quasi peak, measured at 10 m distance |
|
Emission tests Radiated 1…3 GHz |
<76 dB (µV/m) peak <56 dB (µV/m) average, measured at 3 m distance |
|
Emission tests Radiated 3…6 GHz |
<80 dB (µV/m) peak <60 dB (µV/m) average, measured at 3 m distance |
Description |
Type test result |
Reference |
---|---|---|
Overvoltage category |
III |
IEC 60255-27 |
Pollution degree |
3 |
IEC 60255-27 |
Insulation class |
Class I |
IEC 60255-27 |
Dielectric tests |
2 kV, 50 Hz, 1 min 500 V, 50 Hz, 1 min, communication |
IEC 60255-27 IEEE C37.90-2005 |
Impulse voltage test |
5 kV, 1.2/50 μs, 0.5 J 1 kV, 1.2/50 μs, 0.5 J, communication |
IEC 60255-27 IEEE C37.90-2005 |
Insulation resistance measurements |
>100 MΩ, 500 V DC |
IEC 60255-27 |
Maximum temperature of parts and materials |
Tested |
IEC 60255-27 |
Flammability of insulating materials, components and fire enclosures |
OK |
IEC 60255-1 IEC 60255-27 |
Single-fault condition |
OK |
IEC 60255-1 IEC 60255-27 |
Description |
Type test result |
Reference |
---|---|---|
Vibration tests (sinusoidal) |
Class 1 |
IEC 60068-2-6 (test Fc) IEC 60255-21-1 |
Shock and bump test |
Class 1 |
IEC 60068-2-27 (test Ea shock) IEC 60068-2-29 (test Eb bump) IEC 60255-21-2 |
Seismic test |
Class 2 |
IEC 60255-21-3 |
Drop test |
OK |
IEC 60068-2-31 ISTA 1A |
Mechanical durability test
|
OK |
IEEE C37.90-2005 |
Description |
Type test value |
Reference |
---|---|---|
Dry heat test |
|
IEC 60068-2-2 IEC60255-1 IEEE C37.90-2005 |
Dry cold test |
|
IEC 60068-2-1 IEC60255-1 IEEE C37.90-2005 |
Damped heat cyclic test |
|
IEC 60068-2-30 IEC60255-1 |
Change of temperature test |
|
IEC 60068-2-14 IEC60255-1 |
Storage test |
|
IEC 60068-2-1 IEC 60068-2-2 IEC60255-1 IEEE C37.90-2005 |
Damp heat steady state test |
10 days at +40°C, 93% RH |
IEC 60068-2-78 IEC60255-1 |
Air quality test |
H2S - 10 ppb NO2 - 200 ppb CL2 - 10 ppb SO2 - 200 ppb Temperature - 25°C Relative humidity - 75% Duration - 21 days |
IEC 60068-2-60 |
Description |
Reference |
---|---|
LV directive |
EMC Directive 2014/30/EU Low Voltage Directive 2014/35/EU RoHS Directive 2015/863/EU |
Standard |
EN 60255-27 (2014) EN 60255-1 (2009) |
UL listed (E-file: E225502) |
UL508 |
Description |
Reference |
---|---|
EMC directive |
2014/30/EU |
Standard |
EN 60255-26 (2013) |
Description |
---|