| Parameter | Values (Range) | Unit | Step | Default | Description |
|---|---|---|---|---|---|
| Start value | 0.010...1.200 | xUn | 0.001 | 0.500 | Start value |
| Operate delay time | 40...120000 | ms | 10 | 40 | Operate delay time |
| Parameter | Values (Range) | Unit | Step | Default | Description |
|---|---|---|---|---|---|
| Voltage block value | 0.01...1.00 | xUn | 0.01 | 0.20 | Internal blocking level |
| Enable block value |
0=False 1=True |
1=True | Enable Internal Blocking |
| Parameter | Values (Range) | Unit | Step | Default | Description |
|---|---|---|---|---|---|
| Operation |
1=on 5=off |
1=on | Operation Off / On |
| Parameter | Values (Range) | Unit | Step | Default | Description |
|---|---|---|---|---|---|
| Reset delay time | 0...60000 | ms | 1 | 20 | Reset delay time |
| Relative hysteresis | 1.0...5.0 | % | 0.1 | 4.0 | Relative hysteresis for operation |