PSPTUV Settings - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - IEC - ANSI - 12.12.2023

REX610 Technical Manual

Table 1. PSPTUV Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Start value 0.010...1.200 xUn 0.001 0.500 Start value
Operate delay time 40...120000 ms 10 40 Operate delay time
Table 2. PSPTUV Group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Voltage block value 0.01...1.00 xUn 0.01 0.20 Internal blocking level
Enable block value

0=False

1=True

1=True Enable Internal Blocking
Table 3. PSPTUV Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation

1=on

5=off

1=on Operation Off / On
Table 4. PSPTUV Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time
Relative hysteresis 1.0...5.0 % 0.1 4.0 Relative hysteresis for operation