REX610 Technical Manual
Table 1. PREVPTOC Group settings (Basic)
Parameter |
Values (Range) |
Unit |
Step |
Default |
Description |
Start value |
0.05...1.00 |
xIn |
0.01 |
0.75 |
Start value |
Operate delay time |
100...60000 |
ms |
10 |
100 |
Operate delay time |
Table 2. PREVPTOC Non group settings (Basic)
Parameter |
Values (Range) |
Unit |
Step |
Default |
Description |
Operation |
1=on
5=off
|
|
|
1=on |
Operation Off / On |