PHPTUC Operation principle - Arc protection - Back-up protection - Feeder protection - Motor protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - ANSI - IEC - 19.04.2024

REX610 Technical Manual

The function can be enabled and disabled with the Operation setting. The corresponding parameter values are "On" and "Off".

The operation of PHPTUC can be described with a module diagram. All the modules in the diagram are explained in the next sections.

Figure 1. Functional module diagram
image/svg+xmlOPERATELevel detector 1BLOCKSTARTLevel detector 2OPR_AOPR_COPR_BST_AST_CST_BI3PI_AI_BI_CTimert

Level detector 1

This module compares the phase currents (RMS value) to the Start value setting. The Operation mode setting can be used to select the "3-phase" or "1-phase" mode.

If in the "3-phase" mode all the phase current values are less than the value of the Start value setting, the condition is detected and an enable signal is sent to the timer. This signal is disabled after one or several phase currents have exceeded the set Start value value of the element.

If in the "1-phase" mode any of the phase current values are less than the value of the Start value setting, the condition is detected and an enable signal is sent to the timer. This signal is disabled after all the phase currents have exceeded the set Start value value of the element.

Note: The protection relay does not accept the Start value to be smaller than Current block value.

Level detector 2

This is a low-current detection module that monitors the de-energized condition of the protected object. The module compares the phase currents (RMS value) to the Current block value setting. If all the phase current values are less than the Current block value setting, a signal is sent to block the operation of the timer.

Timer

Once activated, the timer activates the START output and the phase-specific ST_X output. The time characteristic is according to DT. When the operation timer has reached the value set by Operate delay time, the OPERATE output and the phase specific OPR_X output are activated. If the fault disappears before the module operates, the reset timer is activated. If the reset timer reaches the value set by Reset delay time, the operate timer resets and the START output is deactivated.

The timer calculates the start duration value START_DUR, which indicates the percentage ratio of the start situation and the set operating time. The value is available through the monitored data view.

The BLOCK signal blocks the operation of the function and resets the timer.