PHPTOV Operation principle - Arc protection - Back-up protection - Feeder protection - Motor protection - Technical Manual - REX610 Protection and control - 1.2 - ANSI - IEC - 19.04.2024

REX610 Technical Manual

The function can be enabled and disabled with the Operation setting. The corresponding parameter values are "On" and "Off".

The operation of PHPTOV can be described using a module diagram. All the modules in the diagram are explained in the next sections.

Figure 1. Functional module diagram

Level detector

The fundamental frequency component of the measured three-phase voltages are compared phase-wise to the set value of the Start value setting. If the measured value is higher than the set value of the Start value setting, the level detector enables the phase selection logic module. The Relative hysteresis setting can be used for preventing unnecessary oscillations if the input signal slightly differs from the Start value setting. After leaving the hysteresis area, the start condition has to be fulfilled again and it is not sufficient for the signal to only return to the hysteresis area.

The Voltage selection setting is used for selecting phase-to-earth or phase-to-phase voltages for protection.

For the voltage IDMT operation mode, the used IDMT curve equations contain discontinuity characteristics. The Curve Sat Relative setting is used for preventing undesired operation.
Note: For a more detailed description of the IDMT curves and the use of the Curve Sat Relative setting, see IDMT curve saturation of overvoltage protection in this manual.

Phase selection logic

If the fault criteria are fulfilled in the level detector, the phase selection logic detects the phase or phases in which the fault level is detected. If the number of faulty phases match with the set Num of start phases, the phase selection logic activates the Timer.

Timer

Once activated, the Timer activates the START output. Depending on the value of the set Operating curve type, the time characteristics are selected according to DT or IDMT.
Note: For a detailed description of the voltage IDMT curves, see IDMT curves for overcurrent protection in this manual.

When the operation timer has reached the value set by Operate delay time in the DT mode or the maximum value defined by the IDMT, the OPERATE output is activated.

When the user-programmable IDMT curve is selected, the operate time characteristics are defined by the parameters Curve parameter A, Curve parameter B, Curve parameter C, Curve parameter D and Curve parameter E.

If a drop-off situation occurs, that is, a fault suddenly disappears before the operate delay is exceeded, the reset state is activated. The behavior in the drop-off situation depends on the selected operate time characteristics. If the DT characteristics are selected, the reset timer runs until the set Reset delay time value is exceeded. If the drop-off situation exceeds the set Reset delay time, the Timer is reset and the START output is deactivated.

When the IDMT operate time curve is selected, the functionality of the Timer in the drop-off state depends on the combination of the Type of reset curve, Type of time reset and Reset delay time settings.

Table 1. Reset time functionality when IDMT operation time curve selected
Reset functionality Setting Type of reset curve Setting Type of time reset Setting Reset delay time
Instantaneous reset Operation timer is “Reset instantaneously” when drop-off occurs “Immediate” Setting has no effect Setting has no effect
Frozen timer Operation timer is frozen during drop-off “Def time reset” “Freeze Op timer” Operate timer is reset after the setReset delay time has elapsed
Linear decrease Operation timer value linearly decreases during the drop-off situation “Def time reset” “Decrease Op timer” Operate timer is reset after the set Reset delay time has elapsed
Figure 2. Behavior of different IDMT reset modes. Operate signal is based on settings Type of reset curve = “Def time reset” and Type of time reset= “Freeze Op timer”. The effect of other reset modes is also presented

The Time multiplier setting is used for scaling the IDMT operate times.

The Minimum operate time setting parameter defines the minimum desired operate time for IDMT. The setting is applicable only when the IDMT curves are used.
Note: The Minimum operate time setting should be used with care because the operation time is according to the IDMT curve, but always at least the value of the Minimum operate time setting. For more information, see IDMT curves for overvoltage protection in this manual.

The Timer calculates the start duration value START_DUR, which indicates the percentage ratio of the start situation and the set operation time. The value is available in the Monitored data view.

Blocking logic

There are three operation modes in the blocking function. The operation modes are controlled by the BLOCK input and the global setting in Configuration > System > Blocking mode which selects the blocking mode. The BLOCK input can be controlled by a binary input, a horizontal communication input or an internal signal of the protection relay's program. The influence of the BLOCK input signal activation is preselected with the global Blocking mode setting.

The Blocking mode setting has three blocking methods. In the "Freeze timer" mode, the operation timer is frozen to the prevailing value, but the OPERATE output is not deactivated when blocking is activated. In the "Block all" mode, the whole function is blocked and the Timers are reset. In the "Block OPERATE output" mode, the function operates normally but the OPERATE output is not activated.
Note: The “Freeze timers” mode of blocking has no effect during the inverse reset mode.