Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Operation |
1=on 5=off |
1=on | Operation Off / On | ||
Power unit Mult |
3=Kilo 6=Mega |
3=Kilo | Unit multiplier for presentation of the power related values | ||
Active power Dir |
1=Forward 2=Reverse |
1=Forward | Direction of active power flow: Forward, Reverse | ||
Reactive power Dir |
1=Forward 2=Reverse |
1=Forward | Direction of reactive power flow: Forward, Reverse | ||
Energy unit Mult |
3=Kilo 6=Mega |
3=Kilo | Unit multiplier for presentation of the energy related values | ||
Pulse quantity | 1...10000000 | Wh/VArh | 1 | 100000 | Pulse quantity for the energy pulse outputs |
Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Forward Wh Initial | 0...999999999 | 1 | 0 | Preset Initial value for forward active energy | |
Reverse Wh Initial | 0...999999999 | 1 | 0 | Preset Initial value for reverse active energy | |
Forward VArh Initial | 0...999999999 | 1 | 0 | Preset Initial value for forward reactive energy | |
Reverse VArh Initial | 0...999999999 | 1 | 0 | Preset Initial value for reverse reactive energy | |
Measurement mode |
1=PhsA, PhsB, PhsC 2=Arone 3=Pos Seq 4=PhsAB 5=PhsBC 6=PhsCA 7=PhsA 8=PhsB 9=PhsC |
1=PhsA, PhsB, PhsC | Selected measurement mode for power calculation | ||
Pulse on time | 0.050...60.000 | s | 0.001 | 1.000 | Energy accumulated pulse ON time in secs |
Pulse off time | 0.050...60.000 | s | 0.001 | 0.500 | Energy accumulated pulse OFF time in secs |