Name | Type | Values (Range) | Unit | Description |
---|---|---|---|---|
DISA_COUNT | BOOLEAN |
0=False 1=True |
Signal for counter disabling | |
FRQ_OPR_CNT | INT32 | 0...2147483647 | Frequent operation counter | |
FRQ_OPR_AL | BOOLEAN |
0=False 1=True |
Frequent operation counter alarm | |
STATUS | Enum |
-1=Not defined 1=Ready 2=InProgress 3=Successful 4=WaitingForTrip 5=TripFromProtection 6=FaultDisappeared 7=WaitToComplete 8=CBclosed 9=CycleUnsuccessful 10=Unsuccessful 11=Aborted |
AR status signal for IEC61850 | |
INPRO_1 | BOOLEAN |
0=False 1=True |
Reclosing shot in progress, shot 1 | |
INPRO_2 | BOOLEAN |
0=False 1=True |
Reclosing shot in progress, shot 2 | |
INPRO_3 | BOOLEAN |
0=False 1=True |
Reclosing shot in progress, shot 3 | |
INPRO_4 | BOOLEAN |
0=False 1=True |
Reclosing shot in progress, shot 4 | |
INPRO_5 | BOOLEAN |
0=False 1=True |
Reclosing shot in progress, shot 5 | |
DISCR_INPRO | BOOLEAN |
0=False 1=True |
Signal indicating that discrimination time is in progress | |
CUTOUT_INPRO | BOOLEAN |
0=False 1=True |
Signal indicating that cut-out time is in progress | |
SUC_RECL | BOOLEAN |
0=False 1=True |
Indicates a successful reclosing sequence | |
UNSUC_CB | BOOLEAN |
0=False 1=True |
Indicates an unsuccessful CB closing | |
CNT_SHOT1 | INT32 | 0...2147483647 | Resetable operation counter, shot 1 | |
CNT_SHOT2 | INT32 | 0...2147483647 | Resetable operation counter, shot 2 | |
CNT_SHOT3 | INT32 | 0...2147483647 | Resetable operation counter, shot 3 | |
CNT_SHOT4 | INT32 | 0...2147483647 | Resetable operation counter, shot 4 | |
CNT_SHOT5 | INT32 | 0...2147483647 | Resetable operation counter, shot 5 | |
COUNTER | INT32 | 0...2147483647 | Resetable operation counter, all shots | |
SHOT_PTR | INT32 | 1...7 | Shot pointer value | |
MAN_CB_CL | BOOLEAN |
0=False 1=True |
Indicates CB manual closing during reclosing sequence | |
SOTF | BOOLEAN |
0=False 1=True |
Switch-onto-fault | |
DARREC1 | Enum |
1=on 2=blocked 3=test 4=test/blocked 5=off |
Status |