Measurement functionality - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - IEC - ANSI - 03.05.2023

REX610 Technical Manual

The functions can be enabled or disabled with the Operation setting. The corresponding parameter values are "On" and "Off".

Some of the measurement functions operate on two alternative measurement modes: "DFT" and "RMS". The measurement mode is selected with the Measurement mode setting. Depending on the measuring function if the measurement mode cannot be selected, the measuring mode is "DFT".

Value reporting

The measurement functions are capable of reporting new values for network control center (SCADA system) based on various functions.
  • Zero-point clamping
  • Deadband supervision
  • Limit value supervision
Note: In the three-phase voltage measurement function VMMXU the supervision functions are based on the phase-to-phase voltages. However, the phase-to-earth voltage values are also reported with the phase-to-phase voltages.
Note: GOOSE is an event based protocol service. Analog GOOSE uses the same event generation functions as vertical SCADA communication for updating the measurement values.

Zero-point clamping

A measured value under the zero-point clamping limit is forced to zero. This allows the noise in the input signal to be ignored. The active clamping function forces both the actual measurement value and the angle value of the measured signal to zero. In the three-phase or sequence measuring functions, each phase or sequence component has a separate zero-point clamping function. The zero-value detection operates so that once the measured value exceeds or falls below the value of the zero-clamping limit, new values are reported.

Table 1. Zero-point clamping limits
Function Zero-clamping limit
Three-phase current measurement (CMMXU) 1% of nominal (In)
Three-phase voltage measurement (VMMXU) 1% of nominal (Un)
Residual current measurement (RESCMMXU) 1% of nominal (In)
Residual voltage measurement (RESVMMXU) 1% of nominal (Un)
Sequence current measurement (CSMSQI) 1% of the nominal (In)
Phase sequence voltage measurement (VSMSQI) 1% of the nominal (Un)
Three-phase power and energy measurement (PEMMXU) 1.5% of the nominal (Sn)
Note: When the frequency measurement function FMMXU is unable to measure the network frequency in the undervoltage situation, the measured values are set to the nominal and also the quality information of the data set accordingly. The undervoltage limit is fixed to 10 percent of the minimum value of UTVTR Secondary voltage setting for the frequency measurement.

Limit value supervision

The limit value supervision function indicates whether the measured value of X_INST exceeds or falls below the set limits. The measured value has the corresponding range information X_RANGE and has a value in the range of 0 to 4:
  • 0: "normal"
  • 1: "high"
  • 2: "low"
  • 3: "high-high"
  • 4: "low-low"
The range information changes and the new values are reported.
Figure 1. Presentation of operating limits

The range information can also be decoded into boolean output signals on some of the measuring functions and the number of phases required to exceed or undershoot the limit before activating the outputs and can be set with the Num of phases setting in the three-phase measurement functions CMMXU and VMMXU. The limit supervision boolean alarm and warning outputs can be blocked.

Table 2. Settings for limit value supervision

Function

Settings for limit value supervision

Three-phase current measurement (CMMXU) High limit A high limit
Low limit A low limit
High-high limit A high high limit
Low-low limit A low low limit
Three-phase voltage measurement (VMMXU) High limit V high limit
Low limit V low limit
High-high limit V high high limit
Low-low limit V low low limit
Residual current measurement (RESCMMXU) High limit A high limit res
Low limit -
High-high limit A Hi high limit res
Low-low limit -
Residual voltage measurement (RESVMMXU) High limit V high limit res
Low limit -
High-high limit V Hi high limit res
Low-low limit -
Sequence current measurement (CSMSQI) High limit Ps Seq A high limit, Ng Seq A high limit, Zro A high limit
Low limit Ps Seq A low limit, Ng Seq A low limit, Zro A low limit
High-high limit Ps Seq A Hi high Lim, Ng Seq A Hi high Lim, Zro A Hi high Lim
Low-low limit Ps Seq A low low Lim, Ng Seq A low low Lim, Zro A low low Lim
Phase sequence voltage measurement (VSMSQI) High limit Ps Seq V high limit, Ng Seq V high limit, Zro V high limit
Low limit Ps Seq V low limit, Ng Seq V low limit, Zro V low limit
High-high limit Ps Seq V Hi high Lim, Ng Seq V Hi high Lim, Zro V Hi high Lim
Low-low limit Ps Seq V low low Lim, Ng Seq V low low Lim
Three-phase power and energy measurement (PEMMXU) High limit -
Low limit -
High-high limit -
Low-low limit -

Deadband supervision

The deadband supervision function reports the measured value according to integrated changes over a time period. In Figure 2 the values are reported at points Y1, Y2, Y3 and Y4. There is no value report at the end of |A3 + A4 + A5 + A6 + A7| because the positive and negative areas counteract each other. The integrated changes, |A3 + A4 + A5 + A6 + A7|, equal approximately zero.

Figure 2. Integral deadband supervision
image/svg+xmlYtValue Reported (1st)Y1Value ReportedA1Y2Value ReportedY3Y4AValue ReportedA2A3A4A5A7A6A3 + A4 + A5 + A6 + A7+… 0A >=pre-set valueA1 >= pre-set valueA2 >= pre-set value

The deadband value used in the integral calculation is configured with the X deadband setting. The value represents the percentage of the difference between the maximum and minimum limit in the units of 0.001 percent x seconds.

The reporting delay of the integral algorithms in seconds is calculated with the formula:
Figure 3. Equation

Example for CMMXU:

A deadband = 2500 (2.5 % of the total measuring range of 40)

I_INST_A = I_DB_A = 0.30

If I_INST_A changes to 0.40, the reporting delay is:

Table 3. Parameters for deadband calculation

Function

Settings

Maximum/minimum (=range)

Three-phase current measurement (CMMXU)

A deadband

40/0 (=40xIn)

Three-phase voltage measurement (VMMXU)

V Deadband

4/0 (=4xUn)

Residual current measurement (RESCMMXU)

A deadband res

40/0 (=40xIn)

Residual voltage measurement (RESVMMXU)

V deadband res

4/0 (=4xUn)

Sequence current measurement (CSMSQI)

Ps Seq A deadband, Ng Seq A deadband, Zro A deadband

40/0 (=40xIn)

Frequency measurement (FMMXU) F deadband 0.04/40

Power and energy calculation

The three-phase power is calculated from the selected voltage and current measurements as described in Table 4. The setting Measurement mode determines which voltage and current measurements are used.

It is also possible to use positive-sequence components for calculating the apparent power, which makes the determination of power insensitive to any asymmetry in currents or voltages.

Table 4. Measured apparent power
Measurement mode setting values Power calculation
PhsA, PhsB, PhsC
Figure 4. Equation
image/svg+xmlSUIUIUIAABBCC=⋅+⋅+⋅***
Arone
Figure 5. Equation
image/svg+xmlSUIUIABABCC=⋅−⋅**
Pos Seq
Figure 6. Equation
image/svg+xmlSUI=⋅⋅311*
PhsAB
Figure 7. Equation
image/svg+xmlSUIIABAB=⋅−()**
PhsBC
Figure 8. Equation
image/svg+xmlSUIIBCBC=⋅−()**
PhsCA
Figure 9. Equation
image/svg+xmlSUIICACA=⋅−()**
PhsA
Figure 10. Equation
image/svg+xmlSUIAA=⋅⋅3*
PhsB
Figure 11. Equation
image/svg+xmlSUIBB=⋅⋅3*
PhsC
Figure 12. Equation
image/svg+xmlSUICC=⋅⋅3*

Depending upon the set Measurement mode, the Power and energy calculation module calculates active power, reactive power and apparent power values from the available set of measurements.

Figure 13. Equation
image/svg+xmlPS=Re()
Figure 14. Equation
Figure 15. Equation
Figure 16. Equation

The calculated powers are available as function outputs S_INST, P_INST, Q_INST and the power factor angle as PF_INST.

Depending on the unit multiplier selected with Power unit Mult, the calculated power values in the monitored data and measurement view are presented in units of kVA/kW/kVAr or in units of MVA/MW/MVAr.

Figure 17. Complex power and power quadrants
Table 5. Power quadrants
Quadrant Current P Q PF Power
Q1 Lagging + + 0…+1.00 +ind
Q2 Lagging - + 0…-1.00 -cap
Q3 Leading - - 0…-1.00 -ind
Q4 Leading + - 0…+1.00 +cap

The active power P direction can be selected between forward and reverse with Active power Dir and correspondingly the reactive power Q direction can be selected with Reactive power Dir. This affects also the accumulated energy directions.

The accumulated energy is calculated separately as forward active ( EA_FWD_ACM), reverse active ( EA_RV_ACM), forward reactive ( ER_FWD_ACM) and reverse reactive ( ER_RV_ACM). Depending on the value of the unit multiplier selected with Energy unit Mult, the calculated power values are presented in units of kWh/kVArh or in units of MWh/MVArh.

When the energy counter reaches its defined maximum value, the counter value is reset and restarted from zero. Changing the value of the Energy unit Mult setting resets the accumulated energy values to the initial values, that is, EA_FWD_ACM to Forward Wh Initial, EA_RV_ACM to Reverse Wh Initial, ER_FWD_ACM to Forward VArh Initial and ER_RV_ACM to Reverse VArh Initial. It is also possible to reset the accumulated energy to initial values through a parameter or with the RSTACM input.

Sequence components

The phase-sequence components are calculated using the phase currents and phase voltages. More information on calculating the phase-sequence components can be found in Calculated measurements in this manual.