Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Start value | 0.01...0.50 | xIn | 0.01 | 0.20 | Start value |
Operate delay time | 100...120000 | ms | 10 | 1000 | Operate delay time |
Operating curve type |
5=ANSI Def. Time 15=IEC Def. Time 17=Inv. Curve A 18=Inv. Curve B |
15=IEC Def. Time | Selection of time delay curve type | ||
Machine time Mult | 5.0...100.0 | 0.1 | 5.0 | Machine related time constant |
Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Operation |
1=on 5=off |
1=on | Operation Off / On | ||
Minimum operate time | 100...120000 | ms | 1 | 100 | Minimum operate time for IDMT curves |
Maximum operate time | 500000...7200000 | ms | 1000 | 1000000 | Max operate time regardless of the inverse characteristic |
Cooling time | 5...7200 | s | 1 | 50 | Time required to cool the machine |
Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Reset delay time | 0...60000 | ms | 1 | 20 | Reset delay time |
Current reference | 0.30...2.00 | xIn | 0.01 | 1.00 | Rated current (Ir) of the machine (used only in the IDMT) |