LOFLPTUC Settings - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - IEC - ANSI - 12.12.2023

REX610 Technical Manual

Table 1. LOFLPTUC Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Start value high 0.01...1.00 xIn 0.01 0.50 Current setting/Start value high
Operate delay time 400...600000 ms 10 2000 Operate delay time
Start value low 0.01...0.50 xIn 0.01 0.10 Current setting/Start value low
Table 2. LOFLPTUC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation

1=on

5=off

1=on Operation Off / On
Table 3. LOFLPTUC Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reset delay time 0...60000 ms 1 20 Reset delay time