Characteristic | Value | |||
---|---|---|---|---|
Operation accuracy |
At the frequency f = fn |
|||
Current measurement: ±1.5 % of the set value or ±0.002 × In Ratio I2f/I1f measurement: ±5.0 % of the set value |
||||
Reset time |
+35 ms / -0 ms |
|||
Reset ratio |
Typically 0.96 |
|||
Operate time accuracy | +35 ms / -0 ms |