ILTCTR Settings - Arc protection - Back-up protection - Feeder protection - Motor protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - ANSI - IEC - 03.05.2023

REX610 Technical Manual

Table 1. ILTCTR Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Primary current 1.0...15000.0 A 0.1 100.0 Rated primary current
Amplitude Corr A 0.9000...1.1000 0.0001 1.0000 Phase A amplitude correction factor
Amplitude Corr B 0.9000...1.1000 0.0001 1.0000 Phase B amplitude correction factor
Amplitude Corr C 0.9000...1.1000 0.0001 1.0000 Phase C amplitude correction factor
Angle Corr A -8.0000...8.0000 deg 0.0001 0.0000 Phase A angle correction factor
Angle Corr B -8.0000...8.0000 deg 0.0001 0.0000 Phase B angle correction factor
Angle Corr C -8.0000...8.0000 deg 0.0001 0.0000 Phase C angle correction factor
Secondary current 0.10...10.00 A 0.01 1.00 Rated secondary current
Table 2. ILTCTR Non group settings (Advanced)
Parameter Values (Range) Unit Step Default Description
Reverse polarity

0=False

1=True

0=False Reverse the polarity of the phase CTs