IDMT curves for undervoltage protection - Arc protection - Back-up protection - Feeder protection - Motor protection - Technical Manual - REX610 Protection and control - 1.2 - ANSI - IEC - 17.02.2023

REX610 Technical Manual

In the inverse-time modes, the operate time depends on the momentary value of the voltage, the lower the voltage, the faster the operate time. The operate time calculation or integration starts immediately when the voltage goes below the set value of the Start value setting and the START output is activated.

The OPERATE output of the component is activated when the cumulative sum of the integrator calculating the undervoltage situation exceeds the value set by the inverse-time mode. The set value depends on the selected curve type and the setting values used. The user determines the curve scaling with the Time multiplier setting.

The Minimum operate time setting defines the minimum operate time possible for the IDMT mode. For setting a value for this parameter, the user should carefully study the particular IDMT curve.