The mode of all the logical nodes in the relay's IEC 61850 data model can be set with Test mode. Test mode activation method can be changed via parameter
in the LHMI. Local/Remote control must be set to "Local" to change Test mode via LHMI.Test mode is also available via IEC 61850 communication. Local/Remote control must be set to "Remote" to change Test mode using IEC 61850.
Test mode |
Description |
Protection BEH_BLK |
Protection BEH_TST |
---|---|---|---|
Normal mode |
Normal operation |
FALSE |
FALSE |
IED blocked |
Protection works as in “Normal mode” but the ACT configuration can be used to block physical outputs to process. Control function commands are blocked. |
TRUE |
FALSE |
IED test |
Protection works as in “Normal mode” but protection functions work in parallel with test parameters |
FALSE |
TRUE |
IED test and blocked |
Protection works as in “Normal mode” but protection functions work in parallel with the test parameter. The ACT configuration can be used to block physical outputs to process. The control function command is blocked. |
TRUE |
TRUE |