FSTADAGGIO Settings - Arc protection - Back-up protection - Feeder protection - Motor protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - ANSI - IEC - 12.12.2023

REX610 Technical Manual

Table 1. FSTADAGGIO Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Ena. ARC Channel

0=False

1=True

0=False To Enable/Disable the Channel
Continuous ARC delay 1...60 sec 1 10 ALARM Delay
Fast ARC BO Conn.

0=Disabled

Disabled To Enable fast ARC

1=DIOAGGIO.SO1

2=DIOAGGIO.SO2

3=DIOAGGIO.CSO1

4=DIOAGGIO.CSO2

5=PSUAGGIO.Output 1

6=PSUAGGIO.Output 2

ARC Sensor type

1=Point type

Point type To Select sensor type

2=Loop type

NA NA NA
Note: User must use only “Point type”. Support for “Loop type” is not available in the current release.