Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Start value Freq> | 0.9000...1.2000 | xFn | 0.0001 | 1.0500 | Frequency start value overfrequency |
Start value df/dt | -0.2000...0.2000 | xFn /s | 0.0001 | 0.0100 | Frequency start value rate of change |
Operate Tm Freq | 80...200000 | ms | 10 | 200 | Operate delay time for frequency |
Operate Tm df/dt | 120...200000 | ms | 10 | 400 | Operate delay time for frequency rate of change |
Operation mode |
1=Freq< 2=Freq> 3=df/dt 4=Freq< + df/dt 5=Freq> + df/dt 6=Freq< OR df/dt 7=Freq> OR df/dt |
1=Freq< | Frequency protection operation mode selection | ||
Start value Freq< | 0.8000...1.1000 | xFn | 0.0001 | 0.9500 | Frequency start value underfrequency |
Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Operation |
1=on 5=off |
1=on | Operation Off / On |
Parameter | Values (Range) | Unit | Step | Default | Description |
---|---|---|---|---|---|
Reset delay Tm Freq | 0...60000 | ms | 1 | 0 | Reset delay time for frequency |
Reset delay Tm df/dt | 0...60000 | ms | 1 | 0 | Reset delay time for rate of change |