Ethernet ports - Arc protection - Back-up protection - Feeder protection - Motor protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - ANSI - IEC - 03.05.2023

REX610 Technical Manual

The protection relay allows the use of a rear port IP address for the station ports on the communication module.

The rear port IP network is assigned to a single Ethernet port and it can be used to make separate networks for different communication protocols or, for example, a separate service network for configuration purposes. Multicast station/bus communication, such as GOOSE, is supported on this interface.

The parameters for setting the rear port IP network are located under Configuration > Communication > Ethernet > Rear port(s).

Table 1. Default rear port IP address parameters

Parameter

Option

Default

Description

Configuration/ Communication/ Ethernet/Rear Port{s)/IP address

0.0.0.0

192.168.2.10

IP address for rear port(s)

Configuration/ Communication/ Ethernet/Rear Port{s)/ Subnet mask

0.0.0.0

255.255.255.0

Subnet mask for rear port(s)

Configuration/ Communication/ Ethernet/Rear Port{s)/Mac address

XX-XX-XX-XX-XX-XX

XX-XX-XX-XX-XX-XX

Mac address for rear port(s)