DARREC Delayed initiation lines - Arc protection - Back-up protection - Feeder protection - Motor protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - ANSI - IEC - 19.04.2024

REX610 Technical Manual

The auto-reclose function consists of six individual auto-reclose initiation lines INIT_1...INIT 6 and three delayed initiation lines:
  • DEL_INIT_2
  • DEL_INIT_3
  • DEL_INIT_4

DEL_INIT_2 and INIT_2 are connected together with an OR-gate, as are inputs 3 and 4. Inputs 1, 5 and 6 do not have any delayed input. From the auto-reclosing point of view, it does not matter whether INIT_x or DEL_INIT_x line is used for shot initiation or blocking.

The auto-reclose function can also open the circuit breaker from any of the initiation lines. It is selected with the Tripping line setting. As a default, all initiation lines activate the OPEN_CB output.

Figure 1. Simplified logic diagram of initiation lines

Each delayed initiation line has four different time settings:

Table 1. Settings for delayed initiation lines
Setting name Description and purpose
Str x delay shot 1 Time delay for the DEL_INIT_x line, where x is the number of the line 2, 3 or 4. Used for shot 1.
Str x delay shot 2 Time delay for the DEL_INIT_x line, used for shot 2.
Str x delay shot 3 Time delay for the DEL_INIT_x line, used for shot 3.
Str x delay shot 4 Time delay for the DEL_INIT_x line, used for shots 4 and 5. Optionally, can also be used with SOTF.