It is possible to create several sequences for a configuration.
Autoreclose sequences for overcurrent and non-directional earth-fault protection applications where high speed and delayed autoreclosings are needed can be as follows:
Example 1
The sequence is implemented by two shots which have the same reclosing time for all protection functions, namely I>>, I> and Io>. The initiation of the shots is done by activating the operating signals of the protection functions.
t HSAR | Time delay of high-speed autoreclosing, here: First reclose time |
t DAR | Time delay of delayed autoreclosing, here: Second reclose time |
t Protection | Operating time for the protection stage to clear the fault |
t CB_O | Operating time for opening the circuit breaker |
t CB_C | Operating time for closing the circuit breaker |
In this case, the sequence needs two CBBs. The reclosing times for shot 1 and shot 2 are different, but each protection function initiates the same sequence. The CBB sequence is described in Table 1 as follows:
Setting name | Setting value |
---|---|
Shot number CBB1 | 1 |
Init signals CBB1 | 7 (lines 1, 2 and 3 = 1+2+4 = 7) |
First reclose time | 0.3 s (an example) |
Shot number CBB2 | 2 |
Init signals CBB2 | 7 (lines 1, 2 and 3 = 1+2+4 = 7) |
Second reclose time | 15.0 s (an example) |
Example 2
There are two separate sequences implemented with three shots. Shot 1 is implemented by CBB1 and it is initiated with the high stage of the overcurrent protection (I>>). Shot 1 is set as a high-speed autoreclosing with a short time delay. Shot 2 is implemented with CBB2 and meant to be the first shot of the autoreclose sequence initiated by the low stage of the overcurrent protection (I>) and the low stage of the non-directional earth-fault protection (Io>). It has the same reclosing time in both situations. It is set as a high-speed autoreclosing for corresponding faults. The third shot, which is the second shot in the autoreclose sequence initiated by I> or Io>, is set as a delayed autoreclosing and executed after an unsuccessful high-speed autoreclosing of a corresponding sequence.
t HSAR | Time delay of high-speed autoreclosing, here: First reclose time |
t DAR | Time delay of delayed autoreclosing, here: Second reclose time |
t l>> | Operating time for the I>> protection stage to clear the fault |
t l> or lo> | Operating time for the I> or Io> protection stage to clear the fault |
t CB_O | Operating time for opening the circuit breaker |
t CB_C | Operating time for closing the circuit breaker |
In this case, the number of needed CBBs is three, that is, the first shot's reclosing time depends on the initiation signal.
If the sequence is initiated from the INIT_1 line, that is, the overcurrent protection high stage, the sequence is one shot long. If the sequence is initiated from the INIT_2 or INIT_3 lines, the sequence is two shots long.
Setting name | Setting value |
---|---|
Shot number CBB1 | 1 |
Init signals CBB1 | 1 (line 1) |
First reclose time | 0.0 s (an example) |
Shot number CBB2 | 1 |
Init signals CBB2 | 6 (lines 2 and 3 = 2+4 = 6) |
Second reclose time | 0.2 s (an example) |
Shot number CBB3 | 2 |
Init signals CBB3 | 6 (lines 2 and 3 = 2+4 = 6) |
Third reclose time | 10.0 s |