CCSPVC Operation principle - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - IEC - ANSI - 19.04.2024

REX610 Technical Manual

The function can be enabled and disabled with the Operation setting. The corresponding parameter values are "On" and "Off".

The operation of CCSPVC can be described with a module diagram. All the modules in the diagram are explained in the next sections.

Figure 1. Functional module diagram
image/svg+xmlFAILBLOCKIRESALARMDifferential currentmonitoringI3PI_AI_BI_CIoTimert

Differential current monitoring

Differential current monitoring supervises the difference between the summed phase currents I_A, I_B and I_C and the reference current I_REF.

The current operating characteristics can be selected with the Start value setting. When the highest phase current is less than 1.0 × In, the differential current limit is defined with Start value. When the highest phase current is more than 1.0 × In, the differential current limit is calculated with the equation.
Figure 2. Equation
image/svg+xmlMAXIAIBICStartvalue(_,_,_)×

The differential current is limited to 1.0 × In.

Figure 3. CCSPVC operating characteristics

When the differential current I_DIFF is in the operating region, the FAIL output is activated.

The function is internally blocked if any phase current is higher than the set Max operate current. When the internal blocking activates, the FAIL output is deactivated immediately. The internal blocking is used for avoiding false operation during a fault situation when the current transformers are saturated due to high fault currents.

The value of the differential current is available in the monitored data view on the LHMI or through other communication tools. The value is calculated with the equation.

Figure 4. Equation
image/svg+xmlIDIFFIAIBICIREF_____=++−

The Start value setting is given in units of ×In of the phase current transformer. The possible difference in the phase and reference current transformer ratios is internally compensated by scaling I_REF with the value derived from the Primary current setting values. These setting parameters can be found in the Basic functions section.

The activation of the BLOCK input deactivates the FAIL output immediately.

Timer

The timer is activated with the FAIL signal. The ALARM output is activated after a fixed 200 ms delay. FAIL needs to be active during the delay.

When the internal blocking is activated, the FAIL output deactivates immediately. However, the ALARM output deactivates after a fixed delay of three seconds.

The function resets when the differential current is below the start value and the highest phase current is more than 5 percent of the nominal current (0.05 × In).

If the current falls to zero when the FAIL or ALARM outputs are active, the deactivation of these outputs is prevented.

The activation of the BLOCK input deactivates the ALARM output.