The parameter Input threshold voltage is used to set the threshold level of the binary inputs. Input pickup voltage determines the voltage level for the activation of the inputs. Input drop-off voltage determines the voltage level for the deactivation of the inputs. The threshold set is applicable for the entire module. Binary inputs are configurable to both AC and DC voltage type.
Parameter |
Values |
Default |
|
---|---|---|---|
Slot specific threshold |
1=True 0=False |
0=False |
|
Input pickup voltage |
DC voltage |
18…176 V |
18 V |
AC voltage |
38...168 V |
38 V |
|
Input drop off voltage |
DC voltage |
16…176 V |
16 V |
AC voltage |
34...168 V |
34 V |
Note: Pickup voltage threshold should be always greater than the drop off voltage.
Note: For AC voltages it is recommended to set a 4 V difference between the pickup and dropoff voltage.