Analog channel configuration - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - IEC - ANSI - 19.09.2022

REX610 Technical Manual

EFxPTOC has one analog group input which must be properly configured.

Table 1. Analog inputs
Input Description
IRES Residual current (measured or calculated)
Note: See the preprocessing function blocks in this document for the possible signal sources.

There are a few special conditions which must be noted with the configuration.

Table 2. Special conditions

Condition

Description

IRES

If connected to IRES_MEAS (function RESTCTR), the residual channel saturation limit is 19 A and 55 A for secondary current setting range of 0.1...3 A and 3...10 A respectively. This should be considered when setting Start value for the function.

Improper analog channel configuration causes a validation error if the analog channels are not completely configured or they do not match with certain settings. For troubleshooting, check the contents of this chapter and also the preprocessing blocks in this document. The configuration can be written to the protection relay once the mismatch is corrected.