Analog channel configuration - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - IEC - ANSI - 03.05.2023

REX610 Technical Manual

SECRSYN has two analog group inputs which must be properly configured.

Table 1. Analog inputs
Input Description
U3P1 Three-phase voltages (bus side)
U3P2 Three-phase voltages (line side)
Note: See the preprocessing function blocks in this document for the possible signal sources.

There are a few special conditions which must be noted with the configuration.

Table 2. Special conditions
Condition Description
U3P1 connected to real measurements The function requires that at least two voltage channels from the bus side are connected.

i.e.

UL1; UL2,

UL1; UL2; UL3 for UTVTR function block

U3P2 connected to real measurements The function requires that one voltage channel from the line side is connected to Analog 4.

i.e.

UL1,

UL1; UL2,

UL1; UL2; UL3 for UTVTR function block

When a single voltage channel is connected on the line side, the VT connection setting of the U3P2 source UTVTR defines whether ph-to-earth or ph-to-ph voltages are used from both sides in checking the conditions. If at least two voltage channels are connected on line side, ph-to-ph voltages are used from both sides in checking the conditions regardless of the VT connection settings of the source UTVTRs.

Improper analog channel configuration causes a validation error if the analog channels are not completely configured or they do not match with certain settings.

For troubleshooting, check the contents of this chapter and also the preprocessing blocks in this document. The configuration can be written to the protection relay once the mismatch is corrected.