Alarm mode alternatives - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - IEC - ANSI - 03.05.2023

REX610 Technical Manual

The ALARM input behavior can be selected with the alarm mode settings from the alternatives "Follow-S", "Follow-F", "Latched-S" and "LatchedAck-F-S". The OK input behavior is always according to "Follow-S". The alarm input latched modes can be cleared with the reset input in the application logic.

Figure 1. Symbols used in the sequence diagrams
image/svg+xml

"Follow-S": Follow Signal, ON

In this mode ALARM follows the input signal value, Non-latched.

Figure 2. Operating sequence "Follow-S"
image/svg+xmlActivatingsignalLED

"Follow-F": Follow Signal, Flashing

Similar to "Follow-S", but instead the LED is flashing when the input is active, Non-latched.

"Latched-S": Latched, ON

This mode is a latched function. At the activation of the input signal, the alarm shows a steady light. After acknowledgement by the local operator pressing any key on the keypad, the alarm disappears.

Figure 3. Operating sequence "Latched-S"
image/svg+xmlActivatingsignalLEDAcknow.

"LatchedAck-F-S": Latched, Flashing-ON

This mode is a latched function. At the activation of the input signal, the alarm starts flashing. After acknowledgement, the alarm disappears if the signal is not present and gives a steady light if the signal is present.

Figure 4. Operating sequence "LatchedAck-F-S"
image/svg+xmlActivatingsignalLEDAcknow.