ARCSARC Settings - Arc protection - Motor protection - Feeder protection - Back-up protection - Technical Manual - REX610 Protection and control - Relion Protection and Control - 1.2 - IEC - ANSI - 12.12.2023

REX610 Technical Manual

Table 1. ARCSARC Group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Phase start value 0.50...40.00 xIn 0.01 2.50 Operating phase current
Ground start value 0.05...8.00 xIn 0.01 0.20 Operating residual current
Operation mode

1=Light+current

2=Light only

3=BI controlled

1=Light+current Operation mode
Table 2. ARCSARC Non group settings (Basic)
Parameter Values (Range) Unit Step Default Description
Operation

1=on

5=off

1=on Operation Off / On