The IEC 61850 data model of the protection relays includes a logical node LD0.GSELPRT1 for the GOOSE communication diagnostic. The counters are also available via the HMI path Monitoring > I/O Status > Communication > GSELPRT1 > Monitoring or PCM600 path Application configuration > Communication > GSELPRT1 > Monitoring.
It is possible to reset the GOOSE communication diagnostics counters via Monitoring > I/O Status > Communication > GSELPRT1 > Monitoring > Reset counters and via the IEC 61850 communication by writing TRUE to the RsCnt.Oper.ctlVal attribute under GSELPRT1.
Table 1. Diagnostics data objects
Data object
Description
Diagnostics information
FrRxCnt
Received messages
When increasing, the protection relay is receiving GOOSE messages.
FrTxCnt
Transmitted messages
When increasing, the protection relay is sending GOOSE messages.
RxStCnt
Received state changes
Received GOOSE messages with a new stNum value
RxSeqCnt
Received sequence number
Received GOOSE retransmissions or heartbeat cycle messages with a new sequence number
RxTestCnt
Received frames with test bit
Received GOOSE frames with the test flag on
StWrnCnt
State errors
Number of notified state number jumps
SeqWrnCnt
Sequence errors
Number of notified sequence number jumps
RxTmOutCnt
Receiver time-outs
Number of notified peer device time-outs
ConfErrCnt
Received ConfRev mismatches
When increasing, there is a mismatch between the received GOOSE frame information and the used GOOSE configuration.
NdsComCnt
Received frames with Needs Commissioning
One peer device Indicates that its configuration is not valid or up-to-date.
DSErrCnt
Errors in received data set
Received data are syntactically wrong, or there are less data in received data set than expected.
Alm
Receiver alarm
Alarm signal value connected to the event and application logic. It is active when one peer device is in time-out.
GOOSE Alarm is activated in the receiver device in certain situations.
Time-out
Configuration revision mismatch
Error in the received data set
The Needs Commissioning bit is active in the received message
Figure 1. Receiving GOOSE data in the protection relays
Figure 2. Receiving GOOSE data with quality in the protection relays