Defining data set entries with the IEC 61850 Configuration tool - Arc protection - Motor protection - Feeder protection - Back-up protection - IEC 61850 Engineering Guide - REX610 Protection and control - 1.1 - IEC - ANSI - 12.12.2023

REX610 IEC 61850 Engineering Guide

  1. Select the Data Sets tab.
  2. Right-click a data set and select Details to add data attributes.
    Figure 1. Adding data attributes

  3. In the data set entry window, select the data attribute to be contained in the data set.
    • Click Append selected to add the data attribute to the end of the data set.
    • Click Insert selected to add the data attribute above the selected row in the data set entries list.
    • To remove a data attribute from the data set, select the data attribute in the data set entries pane and click Removed selected.

Reporting data sets can include status and measurement type of data. Also configuration and setting values can be added to data sets in case required.

Note: It is not recommended to configure input signals of the function blocks in IEC 61850 reports or GOOSE data sets. Report Control Block or GOOSE Control Block should use the function block output signals instead.