Defining GOOSE data set entries with the IEC 61850 Configuration tool - Arc protection - Motor protection - Feeder protection - Back-up protection - IEC 61850 Engineering Guide - REX610 Protection and control - Relion Protection and Control - 1.1 - IEC - ANSI - 03.05.2023

REX610 IEC 61850 Engineering Guide

  1. Select the Data Sets tab.
  2. Right-click a data set and select Details to add data attributes.
    Figure 1. Opening Details
    image/svg+xml
  3. In the Data Set Entry window, select the data attribute or data object present in the data set.
    • Click Append selected to add the data to the end of the data set. To add a data object level entry, select it from the FC section. To add a data attribute level entry, select it from the DA section
    • Click Insert selected to add the data above the selected row in the data set entries list.
    • To remove a data from the data set, select the data in the data set entries pane and click Remove selected.

A maximum of 40 data attributes can be added in total to a IED's GOOSE data sets. Recommendation is to divide the attribute amount to 20 per GOOSE data set, for maximum performance in sender/receiver.

Figure 2. Adding data set entries
image/svg+xml
Note: If a data set has quality attributes, the attributes must be located after the status value of the same data object.
Note: The data attribute entries are single data, such as stVal and q. Data set entries can be also defined on the data object level. Data object level GOOSE entries can only be received of the following CDC types: SPS, SPC, ACD, ACT, DPS and DPC.

After defining the data entries for the data sets, configure the GOOSE control block properties.