Creating report control blocks with the IEC 61850 Configuration tool - Arc protection - Motor protection - Feeder protection - Back-up protection - IEC 61850 Engineering Guide - REX610 Protection and control - 1.1 - IEC - ANSI - 03.05.2023

REX610 IEC 61850 Engineering Guide

  1. Select the IED node in Plant Structure in Project Explorer.
  2. Click the Report Controls tab.
  3. Right-click the area containing the existing report control blocks and select New to add a new report control block.
    Figure 1. Adding a new report control block
    image/svg+xml
  4. Browse to any logical node where the data set is created to define where to place the report control block.
  5. Give a unique name to the report control block.
  6. In the drop-down list, select the previously created data set to link with the RCB.
    Figure 2. Data set drop-down list
    image/svg+xml
  7. Edit the properties and options of the created report control block.
    Figure 3. Report control block properties
    image/svg+xml
Note: Data set entries in a data set linked to the RCB can be modified from the Report Control Block tab by selecting the Data Set Details in the shortcut menu.