Creating data sets with the IEC 61850 Configuration tool - Arc protection - Motor protection - Feeder protection - Back-up protection - IEC 61850 Engineering Guide - REX610 Protection and control - 1.1 - IEC - ANSI - 12.12.2023

REX610 IEC 61850 Engineering Guide

  1. Select Plant Structure in the Project Explorer window.
  2. Right-click the IED node.
  3. Select Client-Server Communication in the drop-down box on the toolbar.
    Figure 1. Selecting Client-Server Communication
    image/svg+xml
  4. Select the Data Sets tab.
  5. Right-click the area containing the data set names and select New to add a new data set.
    Figure 2. Creating a new data set

  6. In the Create New Data Set dialog box, define the LN where to place the data set (accept preselected “LD0/LLN0”) and give the data set a unique name.
    Figure 3. Naming the data set
    image/svg+xml
After creating data sets, define the data set entries (data attributes or data objects) for the data sets.