Configuring RCB clients with the IEC 61850 Configuration tool - Arc protection - Motor protection - Feeder protection - Back-up protection - IEC 61850 Engineering Guide - REX610 Protection and control - Relion Protection and Control - 1.1 - IEC - ANSI - 12.12.2023

REX610 IEC 61850 Engineering Guide

Add and configure the IEDs before configuring the RCB client. The potential clients and their communication configuration should be known for a successful RCB client configuration.
Note: The RCB name is limited to 30 characters (without two-digit index number) for IEC 61850 Edition 2.
  1. In the Plant Structure, click the IED node which is RCB server.
  2. Click Report Controls tab.

    The rows of the Report Controls window show the RCBs configured for the IED.

    The columns of the Report Controls window show the RCB clients configured in the PCM600.

  3. To add or remove clients for a report control block, click the check-box in the grid, corresponding to the client and RCB.

    Five clients at the maximum can be connected to a RCB.

    Figure 1. RCB clients

    1
    RCBs configured for the IED
    2
    RCB clients
Note: The clients are added or removed automatically to the corresponding data sets in the Data Sets tab. Date sets are based on the configuration done in the Reports Controls tab and vice-versa.