- Install the latest Connpack version.
-
If the user wants to update the firmware to the latest version without a change in HW configuration, skip this step.
Otherwise, if a new optional module is to be inserted which is supported by the newer Firmware version:- Turn off the relay.
- Insert the new optional modules.
- Turn the relay on.
- Do a ping test to the relay to check for healthy network connection.
- Select the REX610 instance in the plant structure to be updated with new firmware.
- Set the IP address of the REX610 instance to be the same as the relay’s IP address.
A green check mark on the left of the REX610 instance indicates successful connection.
Note: Before starting the firmware update procedure, do a read operation to store the backup of the configuration from the relay.