Importing ICD or CID files - Arc protection - Motor protection - Feeder protection - Back-up protection - Engineering Manual - REX610 Protection and control - 1.2.1 - IEC - ANSI - 01.07.2024

REX610 Engineering Manual

  1. Select an existing IED to import IEC 61850 files.
  2. From the Files of type list, select the file type of IEC 61850 to be imported (ICD or CID).
    The SCL Import Option dialog box opens.
  3. In the SCL Import Option dialog box, select how the file is to be handled during the import.
    Figure 1. SCL Import Options

    • Click Import Generic IED’s only to protect SCL data to protect the existing IEDs in case the SCD file does not match the original configuration in PCM600.
    • Click Import Generic IED’s as Generic IEC61850 IED’s into Plant Structure if it is known that the file includes additional IEDs that are needed. The IED of type “Generic IEC 61850 IED” is used to integrate these kinds of IEDs into the plant structure, for example.
    • Click Ignore PCM Object Type to update the IED object(s) in PCM600 from the IED type(s) in the SCD file, whether or not the IED type(s) in the SCD file matches the IED object(s) in PCM600. This option can be used, for example, when third party IEDs are included in the system and the SCD file sends GOOSE messages to ABB IEDs included in the project.
    • Click Ignore Substation Section to not import the SSD file part of the SCD file.
  4. Click Import when the definition has been completed.
    A progress view displays the importing procedure.