Exporting ICD or CID files - Arc protection - Motor protection - Feeder protection - Back-up protection - Engineering Manual - REX610 Protection and control - 1.2.1 - IEC - ANSI - 01.07.2024

REX610 Engineering Manual

  1. Select the IED in the Plant Structure view.
  2. Right-click the IED and select Export...
    The Export dialog box opens.
  3. From the Save as type list, select the type of file to export.
    • Configured IED description (.cid) for the IEC 61850 structure as needed for the IED at runtime
    • IED capability description (.icd) for the IEC 61850 structure
    Figure 1. IEC 61850: export IED file type selection
  4. Click Save.
    The SCL Export Options dialog box opens.
  5. Select the export options.
    Figure 2. IEC 61850: export options for ICD files

  6. Change the SCL file version by clicking the Advanced button, if required by the receiving configuration tool.
    Figure 3. SCL export options


  7. Click Export.