REV615 Modbus Point List Manual - Arc protection - Merging unit - Capacitor bank protection - Modbus Communication Manual - Modbus Point List Manual - REV615 Capacitor Bank Protection and Control - Relion 615 series - 5.0 FP1 IEC - IEC - 23.05.2023 - REV615
REV615 Modbus Point List Manual
Copyright
Disclaimer
Conformity
Introduction
This manual
Intended audience
Product documentation
Product documentation set
Document revision history
Related documentation
Symbols and conventions
Symbols
Document conventions
Functions, codes and symbols
Modbus data mappings
Overview
Supported functions
Supported functions in REV615
Indications
Premapped indications
Common data 1
CTRL.CBCILO1 Circuit breaker enable signals (1)
CTRL.CBCSWI1 Circuit breaker (1) mom. position
CTRL.CBCSWI1 Circuit breaker (1) mom+mcd position
CTRL.CBXCBR1 Circuit-breaker control (1)
CTRL.DCSXSWI1 Disconnector position indication (1)
CTRL.DCSXSWI2 Disconnector position indication (2)
CTRL.DCSXSWI3 Disconnector position indication (3)
CTRL.DCXSWI1 Disconnector control (1)
CTRL.DCXSWI2 Disconnector control (2)
CTRL.ESSXSWI1 Earthing switch indication (1)
CTRL.ESSXSWI2 Earthing switch indication (2)
CTRL.ESXSWI1 Earthing switch control (1)
LD0.ARCSARC1 Arc protection (1)
LD0.ARCSARC2 Arc protection (2)
LD0.ARCSARC3 Arc protection (3)
LD0.CCBRBRF1 Circuit breaker failure protection (1)
LD0.CCSPVC1 Current circuit supervision (1)
LD0.CMHAI1 Current total demand distortion (1)
LD0.CMMXU1 Three-phase current measurement (1)
LD0.DEFHPDEF1 Directional earth-fault protection, high stage (1)
LD0.DEFLPDEF1 Directional earth-fault protection, low stage (1)
LD0.DEFLPDEF2 Directional earth-fault protection, low stage (2)
LD0.EFHPTOC1 Non-directional earth-fault protection, high stage (1)
LD0.EFIPTOC1 Non-directional earth-fault protection, instantaneous stage (1)
LD0.EFLPTOC1 Non-directional earth-fault protection, low stage (1)
LD0.EFLPTOC2 Non-directional earth-fault protection, low stage (2)
LD0.LEDGGIO1 Indication LED states Color1/Color2
LD0.LEDGGIO1 Indication LED states OFF/ColorX
LD0.LEDPTRC1 Global conditioning (1)
LD0.MVGAPC1 Move (8 pcs) (1)
LD0.MVGAPC2 Move (8 pcs) (2)
LD0.NSPTOC1 Negative-sequence overcurrent protection (1)
LD0.NSPTOC2 Negative-sequence overcurrent protection (2)
LD0.NSPTOV1 Negative-sequence overvoltage protection (1)
LD0.PHHPTOC1 Three-phase non-directional overcurrent protection, high stage (1)
LD0.PHHPTOC2 Three-phase non-directional overcurrent protection, high stage (2)
LD0.PHIPTOC1 Three-phase non-directional overcurrent protection, instantaneous stage (1)
LD0.PHLPTOC1 Three-phase non-directional overcurrent protection, low stage (1)
LD0.PHPTOV1 Three-phase overvoltage protection (1)
LD0.PHPTOV2 Three-phase overvoltage protection (2)
LD0.PHPTUV1 Three-phase undervoltage protection (1)
LD0.PHPTUV2 Three-phase undervoltage protection (2)
LD0.PHQVVR1 Voltage variation (1)
LD0.PSPTUV1 Positive-sequence undervoltage protection (1)
LD0.RESCMMXU1 Residual current measurement (1)
LD0.RESVMMXU1 Residual voltage measurement (1)
LD0.ROVPTOV1 Residual overvoltage protection (1)
LD0.ROVPTOV2 Residual overvoltage protection (2)
LD0.ROVPTOV3 Residual overvoltage protection (3)
LD0.SEQSPVC1 Fuse failure supervision (1)
LD0.SPCGAPC2 Generic control point (16 pcs) (2)
LD0.SSCBR1 Circuit-breaker condition monitoring (1)
LD0.TCSSCBR1 Trip circuit supervision (1)
LD0.TCSSCBR2 Trip circuit supervision (2)
LD0.TRPPTRC1 Master trip (1)
LD0.TRPPTRC2 Master trip (2)
LD0.VMHAI1 Voltage total harmonic distortion (1)
LD0.VMMXU1 Three-phase voltage measurement (1)
LD0.XAGGIO130 Physical I/O states (AIM card XA130)
LD0.XBGGIO110 Physical I/O states (BIO card XB110)
LD0.XGGIO100 Physical I/O states (PSM card X100)
LD0.XGGIO110 Physical I/O states (BIO card X110)
LD0.XGGIO130 Physical I/O states (BIO card X130)
Unmapped indications
All premapped three-phase protection function stages, operate/phase-dependent objects added
Common data 2
LD0.COLPTOC1 Three-phase overload protection for shunt capacitor banks (1)
LD0.CUBPTOC1 Current unbalance protection for shunt capacitor banks (1)
LD0.DIAGLCCH1 Ethernet supervision (1)
LD0.HCUBPTOC1 Three-phase current unbalance protection for shunt capacitor banks (1)
LD0.IL1TCTR1 Three-phase CT supervision (1)
LD0.IL1TCTR2 Three-phase CT supervision (2)
LD0.INTRPTEF1 Transient/intermittent earth-fault protection (1)
LD0.LDPRLRC1 Load profile record (1)
LD0.MAPGAPC1 Multipurpose protection (1)
LD0.MAPGAPC2 Multipurpose protection (2)
LD0.MAPGAPC3 Multipurpose protection (3)
LD0.MAPGAPC4 Multipurpose protection (4)
LD0.MAPGAPC5 Multipurpose protection (5)
LD0.MAPGAPC6 Multipurpose protection (6)
LD0.MAPGAPC7 Multipurpose protection (7)
LD0.MAPGAPC8 Multipurpose protection (8)
LD0.MAPGAPC9 Multipurpose protection (9)
LD0.MAPGAPC10 Multipurpose protection (10)
LD0.MAPGAPC11 Multipurpose protection (11)
LD0.MAPGAPC12 Multipurpose protection (12)
LD0.MAPGAPC13 Multipurpose protection (13)
LD0.MAPGAPC14 Multipurpose protection (14)
LD0.MAPGAPC15 Multipurpose protection (15)
LD0.MAPGAPC16 Multipurpose protection (16)
LD0.MAPGAPC17 Multipurpose protection (17)
LD0.MAPGAPC18 Multipurpose protection (18)
LD0.MDSOPT1 Runtime counter for machines and devices (1)
LD0.RESTCTR1 Io CT supervision (1)
LD0.RESTVTR1 Uo VT supervision (1)
LD0.RESTVTR2 Uo VT supervision (2)
LD0.RESVMMXU2 Residual voltage measurement (2)
LD0.SPCGAPC1 Generic control point (16 pcs) (1)
LD0.SRCPTOC1 Shunt capacitor bank switching resonance protection, current based (1)
LD0.T2PTTR1 Three-phase thermal overload protection, two time constants (1)
LD0.TRPPTRC3 Master trip (3)
LD0.TRPPTRC4 Master trip (4)
LD0.TRPPTRC5 Master trip (5)
LD0.UL1TVTR1 Three-phase VT supervision (1)
LD0.XARGGIO130 Alarm/warning
LD0.XRGGIO130 Alarm/warning
Registers
Premapped registers
Control structure 1
Control structure 2
Control structure 3
Control structure 4
Control structure 5
Control structure 6
Control structure 7
Control structure 8
Device ID string
Event record structure
Fault record structure header
Fault record data
Protection relay's real-time clock (in local time mode) - read and write (synchronize)
Protection relay's real-time clock (in UTC time mode) - read and write (synchronize)
Indication bits mirrored in registers
SSR1 System status register (1) device health
SSR2 System status register (2) protection relay's mode and state
SSR3 System status register (3) data available 1 (client-dependent)
SSR4 System status register (4) data available 2 (client-dependent, user-definable)
SSR5 System status register (5) device alive register
SSR6 System status register (6) control command status (client-dependent)
System diagnostic values
Time and reason for latest protection relay reset
User-definable bits [Alt.2], visible on 0x,1x,3x and 4x
User-definable registers [Alt.1], visible on 3x and 4x
CTRL.CBCSWI1 Circuit breaker operation counter (1)
LD0.ARCSARCx1 Arc protection (x1)
LD0.CMHAI1 Current total demand distortion (1)
LD0.CMMXU1 Phase current demand values (1)
LD0.CMMXU1 Three-phase current measurement (1)
LD0.CSMSQI1 Sequence current measurement (1)
LD0.FMMXU1 Frequency measurement (1)
LD0.PEMMTR1 Three-phase energy measurements (1)
LD0.PEMMXU1 Power measurement demand values (1)
LD0.PEMMXU1 Three-phase power and energy measurement (1)
LD0.PHQVVR1 Voltage variation (1)
LD0.RESCMMXU1 Residual current demand value (1)
LD0.RESCMMXU1 Residual current measurement (1)
LD0.RESVMMXU1 Residual voltage demand value (1)
LD0.RESVMMXU1 Residual voltage measurement (1)
LD0.SSCBR1 Circuit-breaker condition monitoring (1)
LD0.VMHAI1 Voltage total harmonic distortion (1)
LD0.VMMXU1 Three-phase voltage measurement (1)
LD0.VMMXU1 Voltage demand values (1)
LD0.VSMSQI1 Sequence voltage measurement (1)
Unmapped registers
CTRL.LLN0 Local, Remote, Station, Off and Combinations
LD0.LLN0/LPHD1/LDEV1 System values
LD0.MVI4GAPC1 Integer value move (1)
LD0.SCA4GAPC1 Analog value scaling (1)
LD0.SCA4GAPC2 Analog value scaling (2)
LD0.SCA4GAPC3 Analog value scaling (3)
LD0.SCA4GAPC4 Analog value scaling (4)
LD0.T2PTTR1 Three-phase thermal overload protection, two time constants (1)
LD0.XARGGIO130 RTD input values
LD0.XRGGIO130 RTD input values
Controls
Reset, acknowledge and trigger points
CTRL.CBCSWI1 Circuit breaker control (1)
CTRL.DCXSWI1 Disconnector control (1)
CTRL.DCXSWI2 Disconnector control (2)
CTRL.ESXSWI1 Earthing switch control (1)
LD0.LDEV1 Protection relay's warm reset (1)
LD0.SPCGAPC1 Generic control point (16 pcs) (1)
LD0.SPCGAPC2 Generic control point (16 pcs) (2)
LD0.SRGAPC1 Set-reset (8 pcs) (1)
LD0.SRGAPC2 Set-reset (8 pcs) (2)
Unmapped control points
Glossary