Table 1. Three-phase thermal overload protection, two time constants (T2PTTR) main settings
Parameter Function Value (Range) Step
Temperature rise T2PTTR 0.0...200.0°C 0.1
Max temperature T2PTTR 0.0...200.0°C 0.1
Operate temperature T2PTTR 80.0...120.0% 0.1
Short time constant T2PTTR 6...60000 s 1
Weighting factor p T2PTTR 0.00...1.00 0.01
Current reference T2PTTR 0.05...4.00 × I n 0.01
Operation T2PTTR

1 = on

5 = off

-